Motor Protection Circuit-Breaker
Catalog number: 140M-C2E-B63-CX
Rockwell Automation Authorised Distributor
Circuit-Breaker,Motor Protection,4 - 6.3A,MxRtg MCPs(no OvPrt)is 1200.0A,Frame Size C,Standard Breaking Capacity,No Bus Bar Mount,6.3 A,No Knob Adaptor Modification,for Thermal Overloads,None,None,Std Mgntc Trp (Fxd at 13 x le),None,1 N.O. + 1 N.C.,None,Trigger Constraints,None,(1)1a-1b,LS(H-N):1NO+1NC(BFr)
Pricing: log in to view the price.
Specifications
- Degree of protection (IP)
- IP2X
- Depth (mm)
- 74.500
- Device construction
- Built-in device fixed built-in technique
- Height (mm)
- 90.000
- Number of poles
- 3.000
- Overload release current setting (A)
- 4.0 to 6.3
- Phase failure sensitive
- Y
- Rated operating voltage (V)
- 6.3
- Rated operation power at AC-3, 230 V (kW)
- 1.500
- Rated operation power at AC-3, 400 V (kW)
- 2.200
- Rated short-circuit breaking capacity lcu at 400 V, AC (kA)
- 100.000
- Switch off technique
- Thermomagnetic
- Type of control element
- Turn button
- Type of electrical connection of main circuit
- Screw connection
- Width (mm)
- 45.000
- With integrated auxiliary switch
- N
- With integrated under voltage release
- N
- With thermal protection
- Y